See GMC-I insulation meter   See insulation meter in another brand
View products GMC-I                     Buy      

 

 

(battery-powered insulation tester with test voltages (up to 1000 V) and a measurement range of up to 99.9 GOhm to specifically check the insulation of floors and walls)

The insulation tester is used to measure electrical installations, especially to check the insulation of floors and walls. The measurement value is displayed directly on the insulation tester. The LCD screen field consists of a backlit dot matrix where menus, adjustment options, measurement results, and help texts are presented. Depending on the country where the device is used, the operating menu will appear in the desired country's language.

The insulation tester is very easy to operate. The multifunction key allows one-handed operation to select from the menu and perform the measurement. Basic and secondary functions are selected with the help of four buttons. The five battery symbols from empty to full constantly inform about the current charge status of the batteries or accumulators. Automatic disconnection of the device when the accumulators or batteries are exhausted. Integrated charging control circuit to ensure the charging of NiMH or NiCd accumulators. During self-check, control images can be retrieved, and the indicator LEDs and relays can be checked. The soft plastic coating protects the device from damage due to drops and impacts.

- Quick control of the limit value via indicator lamp

- Automatic range for measuring resistance of

isolation throughout the measurement range and 

quickly determine the insulation value

- Automatic polarity change of the direction of

the current to detect foreign voltages

- Hold function: the value is maintained after release

the measurement key on the screen

- Recording of values sorted by

circuits, distributors, and objects through

alphanumeric input

- Data interface to transmit the values of 

measurement and update with software

- Convenient software protocol, expandable to a

high-range data bank



Medidor de aislamiento de paredes y suelos. 



View / print instructions

for use of the Metriso C

Instruction Manual Metriso C.

Technical specifications Ω

R ISO

Indication range 000 kΩ ... 99,9 GΩ
Control current 1 mA
Measurement ranges 1

2

3
20 kΩ ... 10,0 GΩ

0,20 MΩ ... 10,0 GΩ

> 10,0 GΩ ... 99,9 GΩ
Nominal value / Impedance (related to the

measurement ranges 1, 2, and 3)
UN = 100 V

UN = 250/ 500/ 1000 V

UN = 100/ 250/ 500/ 1000 V
Self-deviation (related to ranges 

of measurement 1, 2, and 3)
± (5 % of the measurement value + 3 D)

± (5 % of the measurement value + 3 D)

± (7% of the measurement value + 3 D)
Operational measurement deviation (related

with measurement ranges 1, 2, and 3)
± (7% of the measurement value + 3 D)

± (7% of the measurement value + 3 D)

± (10 % of the measurement value + 3 D)

U ISO

Indication range 000 V ... 1,20 kV
Measurement range 50 ... 1,00 kV
Valor nominal / Impedancia 5 MΩ
Self-deviation ± (2.5% of the measurement value + 3 D)
Operational measurement deviation ± (5 % of the measurement value + 3 D)

U ~

Indication range 00,0 V ... 500 V
Measurement range 10 ... 500 V
Valor nominal / Impedancia 5 MΩ
Self-deviation ± (2.5% of the measurement value + 3 D)
Operational measurement deviation ± (5 % of the measurement value + 3 D)

f

Indication range 15,0 ... 400 Hz
Measurement range 45 ... 200 Hz
Valor nominal / Impedancia 5 MΩ
Self-deviation ± (0.5% of the measurement value + 3 D)
Operational measurement deviation ± (1.0 % of the measurement value + 3 D)

R LO

Indication range 0,00 ... 9,99 Ω

> 10,0 ... 99,9 Ω
Measurement range 0,15 ... 10 Ω

> 10 ... 100 Ω
Test current IN = 200 mA
Valor nominal / Impedancia U0 = 4,5 V
Self-deviation ± (2.5% of the measurement value + 3 D)

± (8.0 % of the measurement value + 3 D)
Operational measurement deviation ± (5.0 % of the measurement value + 3 D)

± (10.0 % of the measurement value + 3 D)

I B

Indication range 0,00 ... 9,99 mA
Measurement range 0,1 ... 10 mA AC
Valor nominal / Impedancia 2 kΩ
Self-deviation ± (5.0 % of the measurement value + 3 D)
Operational measurement deviation ± (6.0 % of the measurement value + 3 D)

T

Indication range – 10,0 ... + 50,0 °C
Measurement range 0 ... + 40 °C
Self-deviation ± 2 °C

F rot

Indication range 10,0 ... 90,0 %
Measurement range 20,0 ... 80,0 %
Self-deviation ±5 %

Phase control

Indication range LED PE > 100 V
Measurement range 100 ... 500 V
Valor nominal / Impedancia > 100 MΩ / 50 Hz

Features generales

Overload capacity RLO and IB (the electronic protection makes connection difficult when there is external voltage)

U~ (500 V~ permanente)
Temperatura ambiental + 23 °C ± 2 K
Relative humidity 40 ... 60 %
Power supply

4 baby cells of 1.5 V (4 size C) (alkaline-manganese according to IEC LR14) or 4 NiCd batteries

Battery control by the symbols on the screen
Battery saving

the display lighting can be disconnected. The device automatically disconnects after 10 ... 60 seconds without pressing a key. The duration can be selected by the user.

Safety disconnection

The device disconnects when the charge is very low or cannot be connected.

Loading slot

the batteries can be recharged by directly connecting the component to the network in the charging slot

Pantalla

multi-display with 128 x 64 dot matrix (65 mm x 38 mm), illuminated

Interfaz

Infrared interface (SIR / IrDa) bidirectional, half-duplex, 9600 Baud, 1 start bit, 1 stop bit, 8 data bits, no parity, no handshake

Software for data transmission and communication with the insulation meter, to create control protocols on the PC, print and archive (in the shipment)
Dimensions 275 mm x 140 mm x 65 mm
Peso approx. 1.2 kg with batteries
Type of protection

IP 52 housing according to DIN VDE 0470 part 1/EN 60529

Norma

IEC 1010-1:1990, IEC 1010-1/A2:1995, EN 61010-1:1993, EN 61010-1/A2:1995, VDE 0411 part 1, 1994-03, protection class II, pollution degree 2, insulation measurement –1000 V DC – no overvoltage, voltage measurement – 500 V – CAT II, disturbing emission EN 61326:2002 class B, disturbing resistance, EN 61326:2002, EN 61000-4-2: 1995/A1: 1998, performance label A, EN 61000-4-3: 1995/A1: 1998 performance label B

Contents of the shipment

1 METRISO C insulation tester, 1 belt, batteries, 1 pair of measuring cables, 1 program for PC WinProfi, operating instructions

More information:               

Metrological calibration certificate of:

Technical service and maintenance of:
Insulation meter Insulation meter
Certificado de calibración CAL-LCR
International calibration certificate:    220 US$ Preventive maintenance and verification:   35 US$
Calibration certificate from EQUINLAB SAC calibration laboratory - Standard 17025 30 US$ Repair, corrective maintenance, adjustment, update, and validation:                       60 US$

Includes:
** 2-year warranty.
** Discounts for the sale of two or more Insulation meter.
** Metrological calibration certificate for Insulation meter.
** Preventive maintenance, corrective (repair), technical service, and spare parts.
** Sales, maintenance, calibration, certification, and technical service 24 hours.
Envios a: Argentina, Bolivia, Brasil, Chile, Colombia, Costa, Rica, Cuba, Ecuador, El Salvador, Guatemala, Honduras, Mexico, Nicaragua, Panama, Paraguay, Peru, Puerto Rico, Dominican Republic, Uruguay, Venezuela.
Quick contact:     [email protected] mail     [email protected] mail

 