Image of the Ground Resistance Meter without spikes LTW335
Ground meter / bifilar loop tester without disconnection / operation from 50 V to 440 V / loop test with central outlet of 110 V / installation test CAT IV / automatic start operation
The new Megger ground resistance tester / loop impedance tester checks the loop impedance of an electrical circuit under current, meaning no need to disconnect the power supply. The new LTW300 series ground resistance tester offers a bifilar loop testing solution that does not disconnect 30mA RCDs and can be used over a wide voltage range. The new LTW300 series ground resistance tester provides a range of features to make ground loop testing safer and easier.
The impedance of an electrical circuit with current cannot be performed with a continuity tester. Therefore, a ground loop tester must be used. Ground loop testers measure the loop IMPEDANCE of the circuit.
- Prueba bifilar
- Loop test without disconnection
- High current loop test
- Noise detection
- AUTO STAR
- High-resolution test
- PFC viewer
- Bifilar loop tester without disconnection
- Quick bilayer test (high current)
- Applications from 110 V to 280 V
- Applications from 50 V to 440 V
- Prueba Fase a Fase
- Stores test results
- Downloads the results of the same
Technical specifications of the ground meter
Accuracy
All accuracy claims are based on:
Temperatura ambiente
23ºC ±2ºC
Nominal voltage of the power supply
230 Vca ±1%
Voltage measurement
(solo ca)
50V a 440 V
Accuracy
±2% ±1V
Frequency measurement
Rango
25Hz a 99,99Hz
Accuracy
±0,1Hz
A warning will be displayed if the applied voltage exceeds 440V
Damage will occur if the applied voltage exceeds 600V rms
Loop test
Accuracy
±5% ±0.03 ½ at 230 V AC.
±15% ±0.03 ½ at 50 V AC.
Loop test WITHOUT DISCONNECTION and high current
Source voltage
50 V a 440 V (50Hz)
Rango mostrado
0,01 ≈ until 2000 Ω
Accuracy
±5% ±0,03 Ω
Nominal test current
Loop test without disconnection
15mA (en un suministro 230 Vca nominal)
High current loop test
4A (en un suministro 230 Vca nominal)
EN61557
Operating range
0,30 Ω up to 1000 Ω
Predicted fault current (PFC)
Expected fault current = Measured source voltage / loop resistance
Maximum range
Loop test without disconnection 20 KA
High current loop test 20 KA
High-resolution loop test 40 KA
Accuracy derives from loop testing and voltage measurement
Condiciones ambientales
Temperatura
-10°C a +50°C
Humedad
90% non-condensing H.R. at +40°C max.
Storage temperature
-25°C a +70°C
Maximum altitude
2000m for a total safety specification
Entry of dust and water
IP54
Seguridad
IEC61010
Designed according to IEC61010-1
Designed for 300V to Ground Category IV, with Phase to Phase voltages up to 440 V
Fusibles protegidos a 600 V rms ca
EN61557
Complies with the following parts of EN61557, Electrical safety in low voltage systems up to 1000V AC and 1500V DC - Equipment for testing, measuring, or monitoring protective measures:
Parte 1 - Requerimientos generales
Part 3 - Loop resistance
E.M.C
In accordance with IEC61326-1
Power supply
Battery
8 batteries x 1.5 V type IEC LR6 (AA alkaline)
Recargables
8 cells x 1.2V NiCd or NiMH
Battery life: 2000 consecutive tests
Peso
1000g ±10% excluding test connections.
Dimensions
203 x 148 x 78 mm
Contents of the shipment
1 x LTW335 earth resistance meter with measuring probes
1 x Cubierta delantera incorporada
1 x Cubierta impermeable IP54
1 x Durable case
1 x CD with useful information for the user
Information:
Recommendation:
Metrological calibration certificate of:
Technical service and maintenance of:
Grounding meter
Grounding meter
International calibration certificate:
220 US$
Preventive maintenance and verification:
35 US$
Calibration certificate from EQUINLAB SAC calibration laboratory - Standard 17025
30 US$
Repair, corrective maintenance, adjustment, update, and validation:
60 US$
Includes:
** 2-year warranty.
** Discounts for the sale of two or more Grounding meter .
** Metrological calibration certificate for Grounding meter .
** Preventive maintenance, corrective (repair), technical service, and spare parts.
** Sales, maintenance, calibration, certification, and technical service 24 hours.
Envios a:Argentina, Bolivia, Brasil, Chile, Colombia, Costa, Rica, Cuba, Ecuador, El Salvador, Guatemala, Honduras, Mexico, Nicaragua, Panama, Paraguay, Peru, Puerto Rico, Dominican Republic, Uruguay, Venezuela.